New Shangcheng Meter Technology Co., Ltd. , http://www.chinapowermeter.com
      Latest design V shape Single row fans remote condensers
Heat Exchange Finned Coils
All finned coils of remote condensers are produced with copper pipes and aluminium
fins with high efficiency pyramidal corrugation
The frame of finned coils is produced in galvanized steel with thickness suitable to weight
of heat exchanger.
All pipes are expanded on aluminium counter-endplates to avoid any contact between
copper pipes and steel frame and therefore any possible pipe damage.
Endplate holes corresponding to header nipples are larger to avoid that vibrations and
dilatations can damage pipes.
External Frame Carenatura
Condensers are produced with galvanized steel frame, epoxy painted RAL9016.
Fan cowls are high type to get max. performances and min. Noise.
Â
Fan Motors
All Standard fans are 400V - 3F - 50Hz
On request: fans 60 Hz available for all diameters
Fans have external rotor, protection IP54, very high efficiency.
Motors and fans are statically and dynamically balanced.
Â
Declared Capacities
Declared capacities are calculated and tested in our test lab according to ENV327.
Ambient temperature +25°C
Condensation temperature +40°C
Refrigerant R404a
Â
Test
All coils are tested with dry air and are properly degreased.
Standard design pressure is 30 bar. The version with max. design pressure 45 bar is
available for all models
Â
Quick Selection
Condensers can be selected if you know type of compressor, cooling capacity and working
conditions according to following scheme and parameters
 Technical data:
Â
Type
D4-176-4X800
D4-191-4X800
D4-205-4X800
D4-267-6X800
D4-291-6X800
D4-315-6X800
D4-361-8X800
D4-394-8X800
D4-414-8X800
Capacity
Water
35ºC outdoor temp.
Inlet
45ºC,
KW
175.6
190.6
205.4
266.5
291.2
314.6
361.4
394.4
414.4
outlet
40ºC
20% Glycol
Inlet Â
45ºC
171.5
186.5
201.0
258.0
282.3
308.6
352.9
385.6
405.6
outlet
40ºC
Medium
Water flow
M3/h
30.5
33.1
35.7
46.3
50.6
54.7
62.8
68.6
72.1
Pressure drop
kPa
98
84
70
48
39
93
98
82
65
Air flow
M3/h
86771
83195
79955
13054
124786
119924
173533
166376
159905
Fan motor(400V/3N/50HZ)
W
7200
7200
7200
10800
10800
10800
1440
1440
1440
A
15.2
15.2
15.2
22.8
22.8
22.8
30.4
30.4
30.4
Fan
No X φ
2X2X800
2X2X800
2X2X800
2X3X800
2X3X800
2X3X800
2X4X800
2X4X800
2X4X800
Sound pressure level
dB(A)
54.0
54.0
54.0
56.0
56.0
56.0
58.0
58.0
58.0
10m
Dimension
L
mm
2670
2670
2670
3870
3870
3870
5070
5070
5070
W
mm
2250
2250
2250
2250
2250
2250
2250
2250
2250
H
mm
2000
2000
2000
2000
2000
2000
2000
2000
2000
Inlet φ
mm
2X2-1/2"
2X2-1/2"
2X2-1/2"
2X3"
2X3"
2X3"
2X4"
2X4"
2X4"
Inlet φ
mm
2X2-1/2"
2X2-1/2"
2X2-1/2"
2X3"
2X3"
2X3"
2X4"
2X4"
2X4"
Product weight(empty)
kg
698
735
835
1135
1225
1617
1753
1894
2042
 Application:
1, textile, machinery, ceramics, fine chemicals, metallurgy, glass, metal, leather and other manufacturing industries;
2, electroplating, electronics, footwear, printing, plastics, clothing, printing, packaging, food processing industry;
3, hospitals, waiting rooms, schools, waiting rooms, supermarkets, laundry room;
Cooler instance, click to enlarge
1, kitchen, vegetable market, a large entertainment center, underground parking, railway stations and other public places;  greenhouse, flowers, poultry, livestock and other types of farms;
2, the existing air conditioning and blower equipment modification and installation.
3, the requirements of high humidity places (such as textiles, planting, etc.), can be part of the interior installation design.
4, the requirements of low humidity, low humidity and high cleanliness of the place, please carefully consider the suitability of use.